← Database

CVE-2022-31206

CRITICAL CVSS: 9.8 Published: 2022-07-26 Modified: 2026-06-17

Description

The Omron SYSMAC Nx product family PLCs (NJ series, NY series, NX series, and PMAC series) through 2022-005-18 lack cryptographic authentication. These PLCs are programmed using the SYMAC Studio engineering software (which compiles IEC 61131-3 conformant POU code to native machine code for execution by the PLC's runtime). The resulting machine code is executed by a runtime, typically controlled by a real-time operating system. The logic that is downloaded to the PLC does not seem to be cryptographically authenticated, allowing an attacker to manipulate transmitted object code to the PLC and execute arbitrary machine code on the processor of the PLC's CPU module in the context of the runtime. In the case of at least the NJ series, an RTOS and hardware combination is used that would potentially allow for memory protection and privilege separation and thus limit the impact of code execution. However, it was not confirmed whether these sufficiently segment the runtime from the rest of the RTOS.

Affected Platforms

Omron Nx701-1620Omron Nj501-1320Omron Nj101-9020 FirmwareOmron Nj101-1020Omron Nj501-4500 FirmwareOmron Nj501-1420Omron Nx701-Z600 FirmwareOmron Nj501-1420 FirmwareOmron Nj501-1400 FirmwareOmron Nj501-5300-1

Weakness Type

CWE-347