Description

Power Distribution Units running on Powertek firmware (multiple brands) before 3.30.30 have an insecure permissions setting on the user.token field that is accessible to everyone through the /cgi/get_param.cgi HTTP API. This leads to disclosing active session ids of currently logged-in administrators. The session id can then be reused to act as the administrator, allowing reading of the cleartext password, or reconfiguring the device.

Affected Platforms

Powertekpdus Basic Pdu FirmwarePowertekpdus Smart PomsPowertekpdus Piml Pdu FirmwarePowertekpdus Piml PduPowertekpdus Smart Pim FirmwarePowertekpdus Smart Pos FirmwarePowertekpdus Smart PosPowertekpdus Smart Pom FirmwarePowertekpdus Smart PomPowertekpdus Smart Pim

Weakness Type

CWE-732